Keeping your world up and running.®

Fluke i3000s Flex-36 AC Current Clamp, 915 mm (36 in.)

The i3000s Flex is an ac current clamp utilizing the Rogowski principle. It can be used to measure currents up to 3000 A when used in conjunction with oscilloscopes, recorders or data loggers. The flexible and lightweight measuring head allows quick and easy installation in hard to reach areas.

Fluke i3000s Flex-36 AC Current Clamp, 915 mm (36 in.)
Overview
Features
Specs
Models
Accessories
Resources
  • The i3000s Flex is an ac current clamp utilizing the Rogowski principle. It can be used to measure currents up to 3000 A when used in conjunction with oscilloscopes, recorders or data loggers. The flexible and lightweight measuring head allows quick and easy installation in hard to reach areas.

    • Three ranges
      • 30 A
      • 300 A
      • 3000 A, 1, 10 or 100 mV/A output
    • Ideal for current measurement on thick and hard to reach conductors without breaking the circuit
    • Maximum conductor diameter 178 mm (7 in.)
    • CAT III 600 V safety rating

    Also available in pack of 4 for use in Power Quality Analyzers. Click here for more info.

  • Electrical Specification
    Current ranges 30 A
    300 A
    3000 A
    AC rms
    Output sensitivity (AC-coupled) 100 mV
    10 mV
    1mV per A
    Load impedance 100 kΩ minimum
    Accuracy at +25°C: ±1% of range (45 Hz to 65 Hz)
    Linearity 10% to 100% of range: ±0.2% of reading
    Noise 8 mV AC rms (30 A)
    2 mV AC rms (300 A, 3000 A)
    Frequency range 10 Hz to 50 kHz (-3 dB)
    Phase error < ±1° (45 Hz to 65 Hz)
    ±10° (at 20 kHz)
    Position sensitivity with cable > 25 mm from the coupling: ±2% of range
    External field with cable > 200 mm from the head: ±1% of range
    Power supply 2 x AA/MN 1500/LR6 Alkaline, 400 hours, low battery indicator or dedicated external power supply
    Temperature coefficient ±0.08% of reading per °C
    Working voltage see Safety standards section: 600 V AC rms or DC
    General Specifications
    Head circumference 915 mm (36 in.)
    Head cable diameter 14.3 mm (0.56 in)
    Head bend radius 38.1 mm (1.5 in)
    Cable length (head to electronics) 2 m (6.56 ft)
    Output connection 0.5 m cable terminated with safety BNC connector. Supplied with 4mm safety plug adapter
    Operating temperature range -20°C to +90°C (-4°F to 190°F) (head)
    -20°C to +85°C (-4°F to 185°F) (electronics)
    Storage temperature range -40°C to +105°C (-40°F to 221°F) (head)
    -20°C to +85°C (-4°F to 185°F) (electronics)
    Operating humidity 15% to 85% (non-condensing)
    Weight 180 g (0.396 lb) (head)
    190 g (0.419 lb) (electronics)
    Safety standards BS EN 61010-1: 2001
    BS EN 61010-2-032: 2002
    BS EN 61010-031: 2002
    600 Vrms, Category III, Pollution Degree 2
    Use of the probe on uninsulated conductors is limited to 600 V AC rms or DC and frequencies below 1 kHz
    EMC standards EN 61326: 1998 +A1, A2, and A3
    Maximum conductor size 610 mm or 914 mm, depending on model
    • Model
      Model Name Description  
      Fluke i3000s Flex 36 Fluke i3000s Flex-36 AC Current Clamp, 915 mm (36 in.)
      AC Current Clamp, 915 mm (36 in.)
    • Compatible Products
      Model Name Description  
      Fluke 120B Series Industrial ScopeMeter® Hand-Held Oscilloscopes
      Fluke 123 Fluke 123 Industrial ScopeMeter® Hand Held Oscilloscope
      Fluke 123/S Fluke 123/S Industrial ScopeMeter® Hand Held Oscilloscope
      Fluke 124 Fluke 124 Industrial ScopeMeter® Hand Held Oscilloscope
      Fluke 124/S Fluke 124/S Industrial ScopeMeter® Hand Held Oscilloscopes with SCC120 kit
      Fluke 125 Fluke 125 ScopeMeter® Oscilloscopes
      Fluke 125/S Fluke 125/S ScopeMeter® Oscilloscopes with SCC120 kit
    • Manuals
      Title  
      TPS Flex, i310 Flex, i331x Flex, i1730 Flex, i17XX Flex, i430 Flex, I2500 Flex CE Declaration of Conformity Download