Keeping your world up and running.®

Fluke 437 Series II 400 Hz Basic Power Quality and Energy Analyzer

Designed for capturing power quality measurements in avionic and military systems, Fluke 437 Series II is the must-have 400 Hz Quality Analyzer.

Get a Free Demo
Overview
Features
Reviews
Specs
Models
Accessories
Resources
Videos
  • Locating, Predicting, Preventing and Troubleshooting Power Quality Issues – Up to 400 Hz

    Higher power frequencies mean smaller and lighter transformers and motors – a critical factor in avionic and military transport applications where weight is a primary concern. The Fluke 437 Series II Power Quality and Energy Analyzer can show you the cost of energy waste due to poor power quality and is ideal for characterizing power quality, conducting load studies and capturing hard-to-find voltage events over a user-defined period of time. Designed for capturing power quality measurements in avionic and military systems, Fluke 437 Series II is the must-have 400 Hz quality analyzer.

    • 400 Hz operation according to MIL-STD 1399 for use in avionic and military applications
    • Get at-a-glance power quality health data in real-time so you can make better maintenance decisions
    • Measure all three phases and neutral with the included flexible current probes
    • Quickly see how much money you’re losing due to energy waste in terms of real dollars
    • Easily see how motor startups are affecting motor drive performance
    • Highest safety rating in the industry: 600 V CAT IV/1000 V CAT III rated for use at the service entrance.
    • Fluke Connect® compatible* – view data locally on the instrument, via Fluke Connect mobile app and PowerLog 430-II desktop software
  • 400Hz measurement and shipboard power measurement
    If you’re dealing with aviation systems measuring key parameters at 400Hz is a must . The Fluke 437-II provides that capability (and measures at 50 and 60Hz too). is designed for users who need to get to the solution of the power quality problem as quickly as possible so that they can minimize expensive downtime. The shipboard power measurement system analyzes according to MIL-STD 1399 to automatically give a full evaluation of voltage, current and power according to the standard. This evaluation makes measurement and analysis as easy as can be. The measurement process and display of data is optimized to get to the most important information as quickly as possible. Multiple parameters are measured simultaneously and displayed in formats that quickly describe overall power quality health while giving you the detailed information you need to make better maintenance decisions. Data can be quickly accessed as simple digital values, trend graphs that give you fast insight into changes over time, waveforms, phasor diagrams or analyzed and organized into tabular format such as the event data where the magnitude, duration and time stamping enable rapid correlation to the problems you are experiencing.

    PowerWave Data Capture— Quickly identify how motor and generator startups are impacting equipment performance
    With PowerWave data capture you can capture three-phase high resolution voltage and current waveforms for up to five minutes along with detailed RMS voltage and current values. By analyzing the interaction of these values over time you can correlate the effects of voltage, current and frequency during the critical startup of motors and generators. PowerWave even goes beyond the standard power quality measurements allowing you to record half cycle rms values on 8 channels, frequency and instantaneous power (Vrms1/2, Arms1/2, W, Hz and scope waveforms for voltage, amps and watts)

    Advanced Power Quality Health— At-a-glance power quality health data in real-time so you have the data you need, when you need it
    The Fluke 430-II utilizes an integrated Power Quality Health summary that gives you an at-a-glance view of a complete range of power quality issues in real time. With a simple graphical presentation, complete with tolerance limits, you can quickly discover which power quality problems may be present on your electrical system. If you don’t know where to start or what problems might exist the advanced Power Quality Health summary will simplify the task.

    Energy loss Calculator—Calculate money lost to energy waste in terms of real dollars.
    It’s a simple fact, poor power quality can have a big impact on the bottom line. The Fluke 435-II enables you to identify issues and measure energy loss giving you specific insight into the amount of loss in dollars associated things like effective power and with poor power quality characteristics such as reactive power, unbalance, distortion, or neutral current. The 435-II even offers users the flexibility to input cable length and cable diameter so you can calculate loss due to conductor sizing (Or use AUTO mode if you don’t know your cable specification) and enter up to four unique time-dependent daily rates (kWh) for more accurate calculations. Armed with this critical data users can easily justify the investment necessary to take countermeasures.

    Power Inverter Efficiency
    Power inverters take DC current and transform it into AC current, or vice versa. But, what percentage of that power going into the inverter comes out as usable current? Nothing is ever 100% efficient, and the efficiency will vary depending on how much power is being used at the time (with the efficiency generally being greater when more power is being used). Inverters can also lose performance over time and need to be checked. By comparing the input power with the output power you can determine the system efficiency. With the Power Inverter Efficiency feature you can discover just how good is your inverter at converting your DC power to AC (or visa versa).

    AutoTrend - Quickly See the Trend
    With a unique AutoTrend feature you can get fast insight into changes over time. Every displayed reading is automatically and continuously recorded without having to set up threshold levels or having to manually start the process So you can quickly view trends in voltage, current, frequency, power, harmonics or flicker on all three phases plus neutral.

  • Product Specifications
    Volt Model Measurement Range Resolution Accuracy
    Vrms (AC + DC) 1 V to 1000 V phase to neutral 0.01 V ±0.1% of nominal voltage4
    Vpk 1 Vpk to 1400 Vpk 1 V 5% of nominal voltage
    Voltage Crest Factor (CF) 1.0 > 2.8 0.01 ±5%
    Vfund   0.1 V ±0.1% of nominal voltage
    Amps (accuracy excluding clamp accuracy)
    Amps (AC + DC) i430-Flex 1x 5 A to 6000 A 1 A ±0.5% ±5 counts
    i430-Flex 10x 0.5 A to 600 A 0.1 A ±0.5% ±5 counts
    1 mV/A 1x 5 A to 2000 A 1A ±0.5% ±5 counts
    1 mV/A 10x 0.5 A A to 200 A (AC only) 0.1 A ±0.5% ±5 counts
    Apk i430-Flex 8400 Apk 1 Arms ±5%
    1 mV/A 5500 Apk 1 Arms ±5%
    A Crest Factor (CF) 1 to 10 0.01 ±5%
    Amps½ i430-Flex 1x 5 A to 6000 A 1 A ±1% ±10 counts
    i430-Flex 10x 0.5 A to 600 A 0.1 A ±1% ±10 counts
    1 mV/A 1x 5 A to 2000 A 1 A ±1% ±10 counts
    1 mV/A 10x 0.5 A A to 200 A (AC only) 0.1 A ±1% ±10 counts
    Afund i430-Flex 1x 5 A to 6000 A 1 A ±0.5% ±5 counts 
    i430-Flex 10x 0.5 A to 600 A 0.1 A ±0.5% ±5 counts
    1 mV/A 1x 5 A to 2000 A 1 A ±0.5% ±5 counts
    1 mV/A 10x 0.5 A A to 200 A (AC only) 0.1 A ±0.5% ±5 counts
    Hz
    Fluke 437 @ 50 Hz nominal 42.500 Hz to 57.500 Hz 0.001 Hz ±0.01 Hz
    Fluke 437 @ 60 Hz nominal 51.000 Hz to 69.000 Hz 0.001 Hz ±0.01 Hz
    Fluke 437 @ 400 Hz nominal 340.0 Hz to 460.0 Hz 0.1 Hz ±0.1 Hz
    Power
    Watts (VA, var) i430-Flex max 6000 MW 0.1 W to 1 MW ±1% ±10 counts
    1 mV/A max 2000 MW 0.1 W to 1 MW ±1% ±10 counts
    Power Factor (Cos j/DPF)   0 to 1 0.001 ±0.1% @ nominal load conditions
    Energy
    kWh (kVAh, kvarh) i430-Flex 10x Depends on clamp scaling and V nominal ±1% ±10 counts
    Energy Loss i430-Flex 10x Depends on clamp scaling and V nominal ±1% ±10 counts Excluding line resistance accuracy
    Harmonics
    Harmonic Order (n) DC, 1 to 50 Grouping: Harmonic groups according to IEC 61000-4-7
    Inter-Harmonic Order (n) OFF, 1 to 50 Grouping: Harmonic and Interharmonic subgroups according to IEC 61000-4-7
    Volts % f 0.0% to 100% 0.1% ±0.1% ±n x 0.1%
    r 0.0% to 100% 0.1% ±0.1% ±n x 0.4%
    Absolute 0.0 to 1000 V 0.1 V ±5% 1
    THD 0.0% to 100% 0.1% ±2.5%
    Amps % f 0.0% to 100% 0.1% ±0.1% ±n x 0.1%
    r 0.0% to 100% 0.1% ±0.1% ±n x 0.4%
    Absolute 0.0 to 600 A 0.1 A ±5% ±5 counts
    THD 0.0% to 100% 0.1% ±2.5%
    Watts % f or r 0.0% to 100% 0.1% ±n x 2%
    Absolute Depends on clamp scaling and V nominal ±5% ±n x 2% ±10 counts
    THD 0.0% to 100% 0.1% ±5%
    Phase Angle -360° to +0° ±n x 1°
    Flicker
    Plt, Pst, Pst (1 min) Pinst 0.00 to 20.00 0.01 ±5%
    Unbalance
    Volts % 0.0% to 20.0% 0.1% ±0.1%
    Amps % 0.0% to 20.0% 0.1% ±1%
    Mains Signaling
    Threshold Levels Threshold, limits and signaling duration is programable for two signaling frequencies
    Signaling Frequency 60 Hz to 3000 Hz 0.1 Hz  
    Relative V % 0% to 100% 0.10% ±0.4%
    Absolute V 3 s (3 second avg.) 0.0 V to 1000 V 0.1 V ±5% of nominal voltage
    General Specifications
    Case Design Rugged, shock proof with integrated protective holster Drip and dust proof IP51 according to IEC60529 when used in tilt stand position Shock and vibration Shock 30 g, vibration: 3 g sinusoid, random 0.03 g 2 /Hz according to MIL-PRF-28800F Class 2
    Display Brightness: 200 cd/m 2 typ. using power adapter, 90 cd/m 2 typical using battery power Size: 127 x 88 mm (153 mm/6.0 in diagonal) LCD Resolution: 320 x 240 pixels Contrast and brightness: user-adjustable, temperature compensated
    Memory 8 GB SD card (SDHC compliant, FAT32 formatted) standard, upto 32 GB optionally Screen save and multiple data memories for storing data including recordings (dependent on memory size)
    Real-Time Clock Time and date stamp for Trend mode, Transient display, System Monitor and event capture
    Environmental
    Operating Temperature 0°C ~ +40°C; +40°C ~ +50°C excl. battery
    Storage Temperature -20°C ~ +60°C
    Humidity +10°C ~ +30°C: 95% RH non-condensing
    +30°C ~ +40°C: 75% RH non-condensing
    +40°C ~ +50°C: 45% RH non-condensing
    Maximum Operating Altitude Up to 2,000 m (6666 ft) for CAT IV 600 V, CAT III 1000 V
    Up to 3,000 m (10,000 ft) for CAT III 600 V, CAT II 1000 V
    Maximum storage altitude 12 km (40,000 ft)
    Electro-Magnetic-Compatibility (EMC) EN 61326 (2005-12) for emission and immunity
    Interfaces Mini-USB-B, Isolated USB port for PC connectivity SD card slot accessible behind instrument battery
    Warranty Three years (parts and labor) on main instrument, one year on accessories
    View full family specifications »
    1. ±5% if ≥ 1% of nominal voltage ±0.05% of nominal voltage if < 1% of nominal voltage
    2. 50 Hz / 60 Hz nominal frequency according to IEC 61000-4-30
    3. 400 Hz measurements are not supported for Flicker, Mains Signaling and Monitor Mode
    4. For nominal voltage 50 V to 500 V
    • Models
      Model Name Description  
      Fluke 437 Series II 400 Hz Basic Fluke 437 Series II 400 Hz Basic Power Quality and Energy Analyzer
       

      Includes:

      • BC430 Power Adapter
      • International Plug Adapter Set
      • BP290 (Single Capacity Li-ion battery) 28 Wh (7 hours or more)
      • TLS430 Test Lead and Alligator Clip Set
      • WC100 Color Coding Clips and Regional Decals
      • 8 GB SD Card
      • PowerLog on CD (includes operator manuals in PDF format)
      • USB Cable A-B Mini
    • Batteries, Chargers & Adapters
      Model Name Description  
      Fluke BC430 Fluke BC430 Line Voltage Adapter/Battery Charger Fluke Store
      Fluke BP291 Fluke BP291 4800 mAh High Capacity Li-Ion Battery for Fluke 190-Series-II
      Fluke EBC290 Fluke EBC290 External Battery Charger for BP290 and BP291 Fluke Store
    • Clips
      Model Name Description  
      Fluke AC285 Fluke AC285 SureGripTM Alligator Clips Fluke Store
    • Current Clamps
      Model Name Description  
      Fluke i430 Fluke i430 Flex 4 Pack Fluke Store
      Fluke i5sPQ3 Fluke i5sPQ3, 5 A AC Current Clamps, 3-pack Fluke Store
    • Options
      Model Name Description  
      Fluke HH290 Fluke HH290 Hanging Hook for ScopeMeter 190-Series II
    • Test Leads
      Model Name Description  
      Fluke TLS430 Fluke TLS430 – Test Leads and Alligator Clips (4 black, 1 green) Fluke Store
    • Test Leads, Probes & Clips
      Model Name Description  
      Fluke WC100 Fluke WC100 Color Localization Set Fluke Store
    • Wireless Accessories
      Model Name Description  
      FLK-FC-SD CARD Fluke Connect Wireless SD Card
    • Related Products
      Model Name Description  
      Fluke 437 Series II 400Hz Fluke 437 Series II 400 Hz Power Quality and Energy Analyzer
      Fluke 435 Series II Basic Fluke 435 Series II Basic Power Quality and Energy Analyzer
      Fluke 435 Series II Fluke 435 Series II Power Quality and Energy Analyzer
      Fluke 434 II Basic Fluke 434 Series II Basic Energy Analyzer
      Fluke 434 Series II Fluke 434 Series II Energy Analyzer
  •  Product Registration
     