Keeping your world up and running.®

Fluke 1760 Three-Phase Power Quality Recorder

The Fluke 1760 correlates multiple events, and provides undisputable verification in a Class-A compliant package designed for advanced power quality analysis.

Get a Free Demo
  • Fluke 1760 Three-phase Power Quality Recorder with Flexible Current Probes
Overview
Features
Reviews
Specs
Models
Accessories
Resources
  • Class-A compliance for the most demanding power quality tests

    The Fluke 1760 Three-Phase Power Quality Recorder is fully compliant to IEC 61000-4-30 Class-A, for advanced power quality analysis and consistent compliance testing. Designed for analysis of utility and industrial power distribution systems, in medium- and low-voltage networks. The Fluke 1760 provides exceptional flexibility with the ability to customize thresholds, algorithms, and measurement selections. The 1760 power recorder captures the most comprehensive details on user-selected parameters; the supplied PQAnalyze application software enables users uses the in depth measurement and produce sophisticated analysis and reports.

    Applications

    • Detailed disturbance analysis – Perform high-speed transient analysis and uncover root cause of equipment malfunction for later mitigation and predictive maintenance. The fast transient option, with its 6000 V measurement range, allows capture of very short impulses such as capacitor switching and lightning strikes.
    • Class-A quality-of-service compliance – Validate incoming power quality at the service entrance. Thanks to Class A compliance, the Fluke 1760 allows undisputable verification. The Fluke 1760 Class A compliance has been independently verified at a world leading power quality laboratory.
    • Event correlation at multiple locations – Utilizing GPS time synchronization, users can quickly detect where a fault occurred first, either inside or outside the facility. The accuracy of this time-stamping enables users with multiple 1760s on their network to understand the propagation of events across the network.
    • Galvanic separation and DC coupling – Allows complete measurements on dissimilar power systems. For example troubleshoot UPS systems by simultaneously recording the battery voltage and power output.
    • Power quality and power load studies – Assess baseline power quality to validate compatibility with critical systems before installation and verify electrical system capacity before adding loads.
    • Fully Class-A compliant: Conduct tests according to the stringent international IEC 61000-4-30 Class-A standard
    • GPS time synchronization: Correlate data with events or datasets from other instruments with precision
    • Flexible and fully configurable thresholds and scale factors: Allows user to pinpoint specific issues by defining the detailed criteria for detection and recording of disturbances.
    • Uninterrupted power supply (40 minutes): Never miss important events - even record the beginning and end of interruptions and outages to help determine the cause
    • 2 GB data memory: Enables detailed, simultaneous recording of numerous power parameters for long periods of time
    • Comprehensive software included: Provides trend diagrams for root cause analysis, statistical summaries, report writing and real-time data monitoring in the online mode
    • Plug and play: Allows quick setup with automatic sensor detection; sensors are instrument powered, eliminating the need for batteries
    • Rugged field design: Insulated housing and a solid state design with no rotating components enable reliable testing under nearly any conditions

    Product Features:

    • Power quality statistics according to EN50160
    • Voltage event list (dips, swells and interruptions)
    • Continuous recording of:
      • Voltage
      • Current
      • Power P, Q, S
      • Power factor
      • kWh
      • Flicker
      • Unbalance
      • Frequency
      • Voltage and current harmonics to the 50th / Interharmonics
      • THD
      • Mains signaling
    • Triggered recordings
    • Online mode (Oscilloscope, transients and events)
    • 4, 600 V voltage probes
    • 4 dual-range flexible current probes (1000 A / 200 A AC)
    • GPS time sync receiver
    • 2 GB Flash Memory
  • Overview of Measurement Functions
    Statistical evaluation Power quality statistics according to EN50160 and DISDIP tables like ITIC, CEBEMA, ANSI
    Event list Dips, swells and interruptions are detected and stored in the event list. Also any trigger which fires generates an event added to this list.
    The Event list shows the exact time when the event occurred as well as the duration and magnitude. Sorting by several attributes of these events is possible to select one for further root cause analysis.
    RMS values, transients and fast transients can be stored if a trigger fires
    Continuous recording Fluke 1760 records rms values together with corresponding minimum and maximum values for:
    • Voltage
    • Current
    • Power P, Q, S
    • Power Factor
    • kWh
    • Flicker
    • Unbalance
    • Frequency
    • Harmonics/Interharmonics continuously with the following time aggregations: Day, 10 min, Free Interval, e.g.: 15 min, 2 h
    Triggered recordings rms Aggregation time is adjustable between 10 ms (1/2 cycle), 20 ms (1 cycle), 200 ms (10/12 cycles) or 3 sec (150/180 cycles).
    Calculating rms values, Harmonics and Interharmonics is performed synchronous to the power frequency.
    Basic aggregation for harmonics and interharmonics is 200 ms
    Sample rate is 10.24 kHz for all 8 channels
    Mains signalling Phases and N-conductor, Voltage and current
    Online mode Variable refresh rate. This feature allows verification of instrument set up and delivers a quick overview of oscilloscope, transients and events.
    General Data
    Intrinsic uncertainty refers to reference conditions and is guaranteed for two years
    Quality system developed, manufactured as per ISO 9001: 2000
    Environment conditions Operating temp. range 0°C to +50°C; 32°F to +122°F
    Working temp. range -20°C to +50°C; -4°F to +122°F
    Storage temp. range 20°C to +60°C; -4°F to 140°F
    Reference temperature 23°C ±2 K; 74°F ±2 K
    Climatic class B2 (IEC 654-1), -20°C to +50°C; -4°F to +122°F
    Max. operating altitude 2000 m: max. 600 V CAT IV1
    power supply: 300 V CAT III 5000 m: max 600 V CAT III1
    power supply: 300 V CAT II
    1. Depending on sensor
    Reference conditions Environment temperature 23°C ±2 K ; 74°F ±2 K
    Power supply 230 V ±10%
    Power frequency 50 Hz / 60 Hz
    Signal declared input voltage Udin
    Averaging 10 minute intervals
    Housing Insulated, robust plastics housing
    EMC Emission Class-A as per IEC/EN 61326-1
    Immunity IEC/EN 61326-1
    Power supply Range AC: 83 V to 264 V, 45 to 65 Hz
    DC: 100 V to 375 V
    Safety IEC/EN 61010-1 2nd edition
    300 V CAT III
    Power consumption NIMH, 7.2 V, 2.7 Ah
    Battery pack In case of a power supply failure an internal battery maintains the supply for up to 40 minutes. Afterwards, or in case of discharged accumulators the Fluke 1760 is turned off and continues the measurements with the latest settings as soon as the supply voltage returns. The battery can be replaced by the user.
    Display Fluke 1760 features LED indicators for the status of the 8 channels, phase sequence, power supply (mains or accumulator), memory usage, time synchronization, and data transfer.
    Power LED Permanent light: normal power supply from mains.
    OFF: supply via internal accumulator in case of a power failure.
    Channel LEDs 3-color LEDs per channel for Overload condition
    Under load condition
    Data memory 2 GB Flash memory
    Memory model Linear
    Interfaces Ethernet (100 MB/s), compatible to Windows® XP, 7 and 8, RS 232, external modem via RS 232
    Baud rate for RS 232 9600 Baud to 115 kBaud
    Dimensions (H x W x D) 325 x 300 x 65 mm; 2.8 x 11.8 x 2.6 in
    Weight appr. 4.9 kg; 10.8 lbs (without accessories)
    Warranty 2 years
    Calibration interval 1 year recommended for Class-A, otherwise 2 years
    Signal Conditioning
    Range for 50 Hz systems 50 Hz ±15% (42.5 Hz to 57.5 Hz)
    Range for 60 Hz systems 60 Hz ±15% (51 Hz to 69 Hz)
    Resolution 16 ppm
    Sampling frequency for 50 Hz power frequency 10.24 kHz, The sampling rate is synchronized to mains frequency.
    Uncertainty for frequency measurements < 20 ppm
    Uncertainty of internal clock < 1 s / day
    Measurement intervals Aggregation of the interval values as per IEC 61000-4-30 Class-A
    Min-, Max-values Half cycle, e.g.: 10 ms rms values at 50Hz
    Transients Sample rate 100 kHz to 10 MHz per channel
    Harmonics as per IEC 61000-4-7:2002: 200 ms
    Flicker as per EN 61000-4-15:2003: 10 min (Pst), 2 h (Plt)
    Measurement Inputs
    Number of inputs 8 galvanically isolated inputs for voltage and current measurements.
    Sensor safety up to 600 V CAT IV depending on sensor
    Basic safety 300 V CAT III
    Nominal voltage (rms) 100 mV
    Range (peak value) 280 mV
    Overload capacity (rms) 1000 V, continuously
    Voltage rise rate max. 15 kV / µs
    Input resistance 1 MΩ
    Input capacitance 5 pF
    Input filter Each channel is equipped with a passive low-pass filter, an anti-aliasing filter and a 16-bit A/D converter. All channels are sampled synchronously with a common quartz-controlled clock pulse.
    The filters protect against voltage transients and limit the signal rise rate, reduce high frequency components and especially the noise voltage above half the sampling rate of the A/D converter by 80 dB, thus achieving very small measuring errors in an exceptionally large amplitude range. This is also valid under extreme operating conditions like transient voltages at the output of converters.
    Uncertainties
    Uncertainty at reference conditions Uncertainty including the voltage sensors is in compliance with IEC 61000-4-30 Class-A. All voltage sensors are suitable for DC up to 5 kHz
    With Sensor 1000 V 0,1% at Udin = 480 V and 600 V P-N
    Sensor 600 V 0,1% at Udin = 230 V P-N
    Intrinsic uncertainty for harmonics Class I as per EN 61000-4-7:2002
    Reference conditions 23°C ±2 K < 60% rH; 74°F ±2 K < 60% rH
    Warmed up instrument > 3h
    Power supply: 100 V to 250 V AC
    Temperature drift 100 ppm / K
    Aging < 0.05% / year
    Common mode rejection > 100 dB at 50 Hz
    Temperature drift Change of amplification through temperature: < 0.005%/K
    Aging Change of amplification due to ageing: < 0.04%/year
    Noise Noise voltage, input short-circuited: < 40 µV
    DC ±(0.2% rdg + 0.1% sensor)
    • Models
      Model Name Description  
      Fluke 1760 Fluke 1760 Three-Phase Power Quality Recorder
       

      Includes:

      • Input-channels (4 currents/4 voltages or 8 voltages)
      • Internal Flash-memory 2 GB
      • PQ Analyze software on CD-ROM
      • Ethernet cable for network connection (1)
      • Crosslink Ethernet cable for direct PC connection (1)
      • Mains cable (1)
      • Operational manuals
      • Carrying bag
      • Voltage probes, qty 4 (600 V for INTL set, 1000 V for US set)
      • Current probes, qty 4 (Dual-range flexible current probes 1000 A / 200 A AC)
      • GPS time sync receiver
    • CarePlans
      Model Name Description  
      Fluke CarePlans Fluke Handheld Instruments CarePlans Fluke Store
    • Current Clamps
      Model Name Description  
      Fluke TPS Clamp 10A/1A Fluke TPS Clamp 10 A/1 A Clip-on Current Transformer
      Fluke TPS CLAMP 200A/20A Fluke TPS CLAMP 200 A/20 A Clip-on Current Transformer
      Fluke TPS CLAMP 50A/5A Fluke TPS CLAMP 50 A/5 A Clip-on Current Transformer
      Fluke TPS FLEX 18 Fluke TPS FLEX 18 Flexible Current Probe
      Fluke TPS FLEX 24 Fluke TPS FLEX 24 Flexible Current Probe
      Fluke TPS FLEX 36 Fluke TPS FLEX 36 Flexible Current Probe
      Fluke TPS Fluke TPS Shunt 20MA Fluke Store
    • Test Probes
      Model Name Description  
      Fluke TPS Fluke TPS VOLTPROBE 1 KV
      Fluke TPS Fluke TPS VOLTPROBE 10 V Fluke Store
      Fluke TPS Fluke TPS VOLTPROBE 100 V Fluke Store
      Fluke TPS Fluke TPS VOLTPROBE 400 V Fluke Store
      Fluke TPS Fluke TPS VOLTPROBE 600 V Fluke Store
    • Related Products
      Model Name Description  
      Fluke 1760 Fluke 1760 Basic Three-Phase Power Quality Recorder
      Fluke 1760TR Fluke 1760TR Basic Three-Phase Power Quality Recorder
      Fluke 1760TR Fluke 1760TR Three-Phase Power Quality Recorder
  •  Product Registration
     
     Software Downloads

    • Manuals
      Title  
      1760 用户手册 Download
      1760 Users Manual Download
      1760 Mode d'emploi Download
      1760 Bedienungshandbuch Download
      1760 Users Manual Supplement Download
      1760 CE Declaration of Conformity Download
      1760 入门 Download
      1760 Getting Started Download
      1760 Mise en route Download
      1760 Getting Started Download
      1760 Getting Started Supplement Download
      1760 Instruction Sheet Download
      1760 Software 参考手册 Download
      1760 Software Reference Manual Download
      1760 Software Reference Manual Download
      1760 Software Reference Manual Download
      1760 Software Reference Manual Supplement Download
      1760 Statement of Memory Volatility Download
    • Application Notes
      Title  
      Power quality recording and analysis: techniques and applications Download
    • Brochures
      Title  
      Fluke Power Quality Family Brochure Download
      PQ Warning Signs Brochure Download
    • Data Sheets
      Title  
      Fluke 1760 Power Recorder Data Sheet Download