Keeping your world up and running.®

Fluke VR101S

Power quality, power recorder, power event recorder

This product is discontinued or reclassified

Overview
Features
Specs
Models
Resources
  • Set up, plug in, download, and analyze

    Homes, offices, hospitals, and factories depend on electronic devices. And electronic devices depend on good power quality. The Fluke VR101S is the perfect system for catching sags, swells, transients, outages and frequency variations on line voltage at receptacles, where the most sensitive loads are connected. The VR101S is a starter system that includes a compact VR101 event recorder, an optical interface cable, and EventView software that turns your PC into a power quality reporting tool. Additional VR101 event recorders can be purchased individually, so you can monitor several voltage conditions at multiple locations at once.

  • Software for Power Distribution Systems
    International standards define a number of different power distribution systems, TN or IT.

    • TN systems: The most frequently used power distribution systems worldwide are the TN systems. Three phase power distribution with a common earth connection back to the supplying transformer.
    • IT system: The IT-system (Isolated Terra) is in use in Norway (90%), Belgium and some other countries. The differentiation lies in the way the Protective Earth (PE) and the Neutral are treated.



    Setup event parameters


    To set up a VR101 event recorder, just enter the event capture limit parameters on your PC and load them into the recorder. EventView software and the optical interface cable make it easy. Then plug the recorder into the outlet you need to test, and leave it — there's no need to leave a computer hooked up. The compact recorder stores any voltage event that goes outside your limits. The VR101 recorder can store up to as many as 4000 events and a flashing LED tells you when events have been captured.

    Analyze data on your PC


    To get data out of the recorder, hook it back up to your computer. EventView software can download a complete history of the events that occurred while the recorder was plugged into the receptacle. The software lets you build a detailed report of sags, swells, transients, outages and frequency variations with time-stamps and durations. Your PC communicates to the VR101 through an optical interface cable. This means the PC and VR101 are insulated from each other for safety. The event recorder is self-powered by a 7-year lithium battery, so it is not affected by power outages. Each VR101 Recorder has its own real-time clock for time-stamping voltage events and is identified by a unique factory-assigned code. With their clocks and ID codes, multiple recorders can be placed throughout a facility to give a complete picture of power quality.

    Safety conformance

    The VR 101S is protected to EN61010-1, CAT III 300V. CSA and UL listed.

  • Specifications
    Electrical
    Nominal Supply:  120V version: 70V to 140V
       230V version: 140V to 270V
    Nominal Frequencies:  120V version: 50 Hz or 60 Hz
       230V version: 50 Hz or 60 Hz
    Power Consumption:  120V version: 2W
       230V version: 3W
    Sags, Swells and Outage
    Hot-to-neutral  
    Range:  120V version: 0 to 200V
       230V version: 0 to 400V
    Accuracy:  120V version: ±2V rms
       230V version: ±4V rms
    Resolution:  120V version: 1V rms
       230V version: 2V rms
    Neutral-to-groud  
    Range:  120V version: 3 to 200V
       230V version: 3 to 120V
    Accuracy:  120V version: ±2V rms
       230V version: ±2V rms
    Resolution:  120V version: 1V rms
       230V version: 1V rms
    Transient Measurements*
    Hot-to-neutral  
    Range:  100 to 2500V peak
    Accuracy:  ±(10% reading + 10V)
    Resolution:  10V
    Neutral-to-groud  
    Range:  50 to 2500V peak
    Accuracy:  ±(10% reading + 10V)
    Resolution:  10V
    Phase angle  
    Range:  20° to 180°, 200° to 360°
    Accuracy:  ±1°
    Resolution:  1°
    Time Measurements
    Hot-to-neutral  
    Accuracy:  ±0.5 cycles
    Resolution:  0.5 cycles
    Neutral-to-groud  
    Accuracy:  ±1 cycle
    Resolution:  1 cycle
    Events >=1 second
    Accuracy:  ±(2 sec/day + 8 sec)
    Resolution:  8 sec
    Frequency
    Range:  45 to 65 Hz
    Accuracy:  ±0.1 Hz (3 cycles min)
    Resolution:  0.1 Hz
    Note
       *Minimum pulse width: 1 µs
    Environmental Specifications
    Operating Temperature
       -40 to 70ºC (-40 to 160 ºF)
    Humidity (Without Condensation)
       0 to 95%
    Safety Specifications
    Safety
       Protected to EN61010-1
       CAT III 300 V
       CSA and UL listed
    Mechanical & General Specifications
    Size
       85 mm x 68 mm x 35 mm (3.35 in x 2.65 in x 1.35 in)
    Weight
       120 g
    Warranty
       1 year
    Battery Life
       ± 4 years
    Battery type
       3.5V lithium (non-replaceable)
    Memory size
       4000 events
    Computer Hardware Requirements
       IBM PC or 100% compatible with Windows® 3.1, Windows® NT or Windows® 95/98 installed and operating
       At least one free RS-232 serial port
       A pointing device (recommended)
       2 MB hard drive space
       4 MB RAM (8 MB for Windows 95/98)
    • Model
      Model Name Description  
      Fluke VR101S Fluke VR101S

      Voltage Event Recorder with instruction sheet

    • Manuals
      Title  
      VR101S 用户手册 Download
      VR101S Handleiding Download
      VR101S Users Manual Download
      VR101S Mode d'emploi Download
      VR101S Bedienungshandbuch Download
      VR101S Manuale per l’uso Download
      VR101S Manual de uso Download
      VR101 Instruction Sheet Download