Fluke 1630 Earth Ground Clamp Meter

The Fluke 1630 simplifies earth ground loop testing and enables non-intrusive leakage current measurement using a technique that does not require breaking the circuit.

Fluke 1630 Earth Ground Clamp
  • Fluke 1630 Earth Ground Clamp
  • Fluke 1630 Earth Ground Clamp in Case with Accessories
  • Fluke 1630 Earth Ground Clamp in Rugged Case
  • Taking an earth ground measurement with a 1630
Overview
Features
Reviews
Specs
Models/Accessories
Resources
  • The clamp-on ground testing technique used by the Fluke 1630 simplifies ground loop testing and enables non-intrusive leakage current measurement. The compact and rugged design makes the Fluke 1630 easy to use in small places and harsh environments, while the ‘display hold’ and the continuity testing with an audible alarm function ensures convenience in use. The novel technique means that earth ground loop testing and continuity testing can be completed without breaking the circuit.

    Stakeless testing system

    The Fluke 1630 uses the Stakeless testing method, which eliminates the need to disconnect parallel ground rods and find suitable locations for placing auxiliary ground stakes. This saves time and enables users such as industrial and utility electricians, and field service electricians and contractors, to perform earth ground loop tests in locations where it is not possible to use other techniques, including inside buildings or on power pylons. With the Stakeless testing method, earth ground stakes are no longer necessary. The Fluke 1630 Earth Ground Clamp is placed around the earth ground rod or the connecting cable. A known voltage is induced by one half of the clamp and the current is measured by the other half. The tester automatically determines the ground loop resistance at this grounding connection.

    • A wide ground loop resistance range, from 0.025 Ω to1500 Ω, to satisfy all requirements
    • Large jaw opening of 35 mm (1.38 in) for tests on ground conductors and/or equipotential bus bars
    • Measurement of ground leakage current, from 0.2 mA to 1000 mA, without needing to disconnect - ideal for system troubleshooting
    • Wide AC current measurement range from 0.2 A to 30 A allows one instrument for multiple applications
    • User-defined HI / LO Alarm limits, for rapid measurement evaluation
    • Handy ‘display hold’ button for capturing readings in hard-to-reach places
    • Time saving memory function automatically records and stores measured values
    • Automatic self calibration ensures correct measurement every time
    • Overload protection: 200 A
    • Carrying case and resistance test loop included
    • ≥ 8 hours battery life (continuous operation)
  • General Specifications
    Operating error Refers to the operating temperature range and is guaranteed for 2 years
    Storage temp. range -20°C to 60°C (-4°F to 140°F)
    Reference temp. range 23°C ±5°C (73°F ±9°F)
    Storage humidity < 75% Rh
    Operating humidity < 85% Rh
    Display 999 digital LC display with special symbols
    Protection IP30 according to IEC 529/EN 60529
    Safety 300 V, CAT III pollution degree 2 IEC 61010-1 and IEC 61010-2-032
    Weight 750 g (1.165 lbs)
    Conductor size 35 mm (1.38 in) approximately
    Dimension (L x W x D) 276 x 100 x 47 mm (10.8 x 3.9 x 1.9 in)
    Emission IEC 1000 4-2, IEC 61326-I class B
    Immunity IEC 61000-4-2, 8 kV (air) criteria A
    IEC 61000-4-3, 3 V/m performance criteria A
    Range selection Auto
    Overload indicator "OL" on display
    Measuring time 0.5 sec
    Measuring frequency 3.333 kHz
    Battery type 9 V alkaline (type IEC 6 LR 61)
    Battery life ≥ 8 hours (continuous operation)
    Power consumption 40 mA
    Low battery indication Display symbol
    Ground Loop Resistance (Autorange)
    Range Accuracy
    (±% of reading Ω)
    0.025 - 0.250 Ω ±1.5% rdg ±0.02 Ω
    0.250 - 9.999 Ω ±1.5% rdg ±0.05 Ω
    10.00 - 99.99 Ω ±2.0% rdg ±0.3 Ω
    100.0 - 199.9 Ω ±3.0% rdg ±1.0 Ω
    200.0 - 400.0 Ω ±5.0% rdg ±5 Ω
    400.0 - 600.0 Ω ±10% rdg ±10 Ω
    600.0 - 1500 Ω ±20%
    Loop resistance with no inductance, external magnetic field < 50A/m, external electrical field < 1 V/m, conductor centered.
    • Models
      Model Name Description  
      Fluke 1630 Fluke 1630 Earth Ground Clamp Meter
       

      Includes:

      • Rugged carrying case with shoulder strap
      • Resistance test loop
      • 9 V battery
      • User's manual
    • CarePlans
      Model Name Description  
      Fluke-G2P-Group2 Fluke G2P-Group2 Gold CarePlan Fluke Store
      Fluke-S2P-Group2 Fluke S2P-Group2 Silver CarePlan Fluke Store
    • Manuals
      Title  
      1630 Users Manual Download
      1630 User's Manual Supplement Download
      1630 Statement of Memory Volatility Download
      1630 Calibration Information Download
      1630 用户手册 Download
      1630 Handleiding Download
      1630 Bedienungshandbuch Download
      1630 Manuale per l’uso Download
      1630 Instrukcja użytkownika Download
      1630 Manual do usuário Download
      1630 Users Manual Download
      1630 Mode d'emploi Download
      1630 Uživatelská příručka Download
      1630 Manual de uso Download
    • Application Notes
      Title  
      Principles of earth grounding Download
      Checking ground electrode impedance for commercial, industrial and residential buildings Download
      Maintaining a solid ground Download
      How to use cable and pole earth ground testers Download
    • Data Sheets
      Title  
      Fluke 1630 Data Sheet Download
    • Demos
      Title  
      Earth Ground Resistance - Principles, Testing Methods and Applications Download
      Fluke 1621/1623/1625 Virtual Demo Download
×
×
×