Fluke Set of 3 5A/50A Current Clamps

Fluke Set of 3 5A/50A Current Clamps
Overview
Specs
Models
Accessories
Resources
  • Expand the capabilities of the Fluke 1735 and Fluke 1740 Series Loggers with the dual-range 5 A/50 A current clamps. The accessory includes three precision clamps that are automatically detected and scaled by the instrument when attached.

  • Specifications
    Electrical characteristics Nominal current in 50 A AC rms
    Overload up to 100 A rms
    Conductor position influence < 0.5% of range at 50/60 Hz
    Error due to adjacent conductor ≤ 15 mA/A at 50 Hz
    Phase shift at 2 kHz at 200 A < ±1°
    Frequency range 40 Hz to 10 kHz (-3 dB)
    Temperature coefficient 0.015% of range / °C
    Working voltage (see section safety) 600 V AC rms or DC
    Order reference 1-phase: EP0442A
    3-phase: EP0452A
    3-phase+N: EP0453A
    Accuracy Primary current 0.125 A to 2.5 A Operating error in % of reading: ±2.5%
    Phase shift: not specified
    Primary current 2.5 A to 12.5 A Operating error in % of reading: ±1.5%
    Phase shift: < 2°
    Primary current 12.5 A to 25 A Operating error in % of reading: ±0.5%
    Phase shift: < 0.5°
    Primary current 25 A to 50 A Operating error in % of reading: ±0.5%
    Phase shift: < 1°
    General characteristics Maximum conductor size 15 mm diameter, bus bar 15 x 17 mm
    Cable length 2 m
    Operating temperature range -10°C to +55°C
    Storage temperature range -20°C to +70°C
    Operating humidity 15% to 85% rh (non condensing)
    Weight (per clamp) 175 g
    Reference conditions Environment temperature range +18°C to +26°C
    Humidity 20% to 75% r.h.
    Current sinusoidal waveform, 48 to 65 Hz, distortion factor: < 1%, no DC component
    Load impedance for voltage output ≥ 1 MΩ, <100 pF
    Safety standards IEC/EN61010-1: 2001
    IEC/EN61010-2-032
    IEC/EN61010-2-031
    Safety 600 V CAT III, pollution degree 2
    The application of the clamps on uninsulated conductors is limited to 600 V rms or DC to ground and frequencies below 1 kHz.
    EMC standards EN61326-1: 1997/A1: 1998
    Dimensions 102 x 42.5 x 23.5 mm
    • Model
      Model Name Description  
      Fluke MBX Clamp 5A/50A Fluke Set of 3 5A/50A Current Clamps
      Set of 3 5A/50A Current Clamps
    • Compatible Products
      Model Name Description  
      Fluke 1735 Fluke 1735 Three-Phase Power Quality Logger
    • Manuals
      Title  
      5A/50A Instruction Sheet Download