Fluke Set of 3 20A200A Current Clamps

This product is discontinued or reclassified

Overview
Specs
Models
Resources
  • Expand the capabilities of the Fluke 1735 and Fluke 1740 Series Loggers with the dual-range 20 A/200 A current clamps. The accessory includes three precision clamps that are automatically detected and scaled by the instrument when attached.

  • Specifications
    Electrical characteristics Nominal current in 200 A AC rms
    Overload up to 300 A rms
    Conductor position influence < 0.5% of range at 50/60 Hz
    Error due to adjacent conductor <= 15 mA/A at 50 Hz
    Phase shift at 2 kHz at 200 A < ± 1 degree
    Frequency range 40 Hz to 10 kHz (-3 dB)
    Temperature coefficient 0.015% of range / °C
    Working voltage (see section safety) 600 V AC rms or DC
    Order reference 1-phase: EP0443A
      3-phase: EP0455A
      3-phase+N: EP0456A
    Accuracy Primary current 0.5 A to 10 A Operating error in % of reading: ± 2.5%
      Phase shift: not specified
    Primary current 10 A to 50 A Operating error in % of reading: ± 1.5%
      Phase shift: < 2°
    Primary current 50 A to 100 A Operating error in % of reading: ± 0.5%
      Phase shift: < 0.5°
    Primary current 100 A to 200 A Operating error in % of reading: ± 0.5%
      Phase shift: < 1°
    General characteristics Maximum conductor size 15 mm diameter, bus bar 15 x 17 mm
    Cable length 2 m
    Operating temperature range -10 °C to +55 °C
    Storage temperature range -20 °C to +70 °C
    Operating humidity 15% to 85% r.h. (non condensing)
    Weight (per clamp) 175 g
    Reference conditions Environment temperature range +18 °C to +26 °C
    Humidity 20% to 75% r.h.
    Current sinusoidal waveform, 48 to 65 Hz, distortion factor: < 1%, no DC component
    Load impedance for voltage output => 1 MΩ, <100 pF
    Safety standards IEC/EN61010-1: 2001
    IEC/EN61010-2-032
    IEC/EN61010-2-031
    Safety 600 V CAT III, pollution degree 2
    The application of the clamps on uninsulated conductors is limited to 600V r.m.s. or DC to ground and frequencies below 1kHz
    EMC standards EN61326-1: 1997/A1: 1998
    Dimensions 102 x 42.5 x 23.5 mm
    • Model
      Model Name Description  
      Fluke MBX Clamp 20A/200A Fluke Set of 3 20A200A Current Clamps
      Set of 3 20A/200A Current Clamps