  • The i3000s Flex is an AC current clamp utilizing the Rogowski principle. It can be used to measure currents up to 3000 A when used in conjunction with oscilloscopes, recorders or data loggers. The flexible and lightweight measuring head allows quick and easy installation in hard to reach areas.

    • Three ranges
      • 30 A
      • 300 A
      • 3000 A, 1, 10 or 100 mV/A output
    • Ideal for current measurement on thick and hard to reach conductors without breaking the circuit
    • Maximum conductor diameter 178 mm (7 in)
    • CAT III 600 V safety rating
  • Electrical Specifications
    Current ranges 30 A
    300 A
    3000 A
    AC rms
    Output sensitivity (AC-coupled) 100 mV
    10 m
    1 mV per A
    Load impedance 100 kΩ minimum
    Accuracy at +25°C
    ±1% of range (45 Hz to 65 Hz)
    Linearity 10% to 100% of range
    ±0.2% of reading
    Noise 8 mV AC rms (30 A)
    2 mV AC rms (300 A, 3000 A)
    Frequency range 10 Hz to 50 kHz (-3 dB)
    Phase error < ±1° (45 Hz to 65 Hz)
    ±10° (at 20 kHz)
    Position sensitivity with cable > 25 mm from the coupling
    ±2% of range
    External field with cable > 200 mm from the head
    ±1% of range
    Power supply 2 x AA/MN 1500/LR6 Alkaline, 400 hours, low battery indicator or dedicated external power supply
    Temperature coefficient ±0.08% of reading per °C
    Working voltage see safety standards section
    600 V AC rms or DC
    General Specifications
    Head circumference 610 mm (24in)
    Head cable diameter 14.3 mm (0.56in)
    Head bend radius 38.1 mm (1.5in)
    Cable length (head to electronics) 2 m (6.56 ft)
    Output connection 0.5 m cable terminated with safety BNC connector. Supplied with 4mm safety plug adapter
    Operating temperature range -20°C to +90°C (-4°F to 190°F) (head)
    -20°C to +85°C (-4°F to 185°F) (electronics)
    Strong temperature range -40°C to +105°C (-40°F to 221°F) (head)
    -20°C to +85°C (-4°F to 185°F) (electronics)
    Operating humidity 15% to 85% (non-condensing)
    Weight 180 g (0.396 lb) (head)
    190 g (0.419 lb) (electronics)
    Safety standards BS EN 61010-1: 2001
    BS EN 61010-2-032: 2002
    BS EN 61010-031: 2002
    600 Vrms, Category III, Pollution Degree 2
    Use of the probe on uninsulated conductors is limited to 600 V AC rms or DC and frequencies below 1 kHz
    EMC standards EN 61326: 1998 +A1, A2, and A3
    Maximum conductor size 610 mm or 914 mm, depending on model